NPCF Week(6/17-6/23)
- F&S started VFDs annual preventive maintenance, it will take a week or so to complete, this is will not impact critical equipment but will impact office and mechanical rooms ventilation.
- brought in an outside mechanical contractor to estimate the cost to preform boilers tune up to verify combustion safeties and boiler setting.
NPCF Week(6/10-6/16)
- Site experienced power event that impacted Feed A which caused Blue Waters and industry systems productions to reboot.
- Event was caused by lighting activities that impacted Ameren transmission lines.
- This event was not reported by the site power monitoring meters due to network filtering their email as spam, F&S has fixed the problem and reporting has been resumed
- Reviewed power feed to the industry system, found out that most of the racks power are not redundant.
- Resolved CRAH units alram
- Working on to have an outside contract to tup up the boilers
- Continues to cycle pump to inject biocide to inhibit bacteria growth.
- Getting pricing form F&S to install PPC4
...