NPCF Week(6/17-6/23)

  • F&S started  VFDs annual preventive maintenance, it will take a week or so to complete, this is will not impact critical equipment but will impact office and mechanical rooms ventilation. 
  • brought in an outside mechanical contractor to estimate the cost to preform boilers tune up to verify combustion safeties and boiler setting. 

NPCF Week(6/10-6/16)

  • Site experienced power event that impacted Feed A which caused Blue Waters and industry systems productions to reboot.  
  • Event was caused by lighting activities that impacted Ameren transmission lines.
  • This event was not reported by the site power monitoring meters due to network filtering their email as spam, F&S has fixed the problem and reporting has been resumed
  • Reviewed power feed to the industry system, found out that most of the racks power are not redundant.
  • Resolved CRAH units alram
  • Working on to have an outside contract to tup up the boilers
  • Continues to cycle pump to inject biocide to inhibit  bacteria growth.
  • Getting pricing form F&S to install PPC4

...